Please use this identifier to cite or link to this item: https://hdl.handle.net/20.500.12104/44156
Title: Regulation of the organic pollution level in anaerobic digesters by using off-line COD measurements
Author: Mendez-Acosta, H.O.
Garcia-Sandoval, J.P.
Gonzalez-Alvarez, V.
Alcaraz-Gonzalez, V.
Jauregui-Jauregui, J.A.
Issue Date: 2011
Abstract: A sampled delayed scheme is proposed to regulate the organic pollution level in anaerobic digestion processes by using off-line COD measurements. The proposed scheme is obtained by combining an error feedback control with a steady state estimator to track constant references and attenuate process load disturbances. The controller performance is tested experimentally for the treatment of tequila vinasses over a period of 68. days under different set-point values and several uncertain scenarios which include badly known kinetic parameters and load disturbances. Experimental results show that the COD concentration can be effectively regulated under the influence of set-point changes and high load disturbances by using only a daily off-line COD measurement, which makes the industrial application of the proposed control scheme feasible. � 2011 Elsevier Ltd.
URI: http://www.scopus.com/inward/record.url?eid=2-s2.0-79960847677&partnerID=40&md5=85d63dd39599d733defa1caa7f33c8f2
http://ovidsp.ovid.com/ovidweb.cgi?T=JS&CSC=Y&NEWS=N&PAGE=fulltext&D=medl&AN=21683577
http://hdl.handle.net/20.500.12104/44156
Appears in Collections:Producción científica UdeG

Files in This Item:
There are no files associated with this item.